CENTUM Registry Entries
|
Registry Key |
Data Type |
Default Value |
Description |
|
ACG10S_DAP |
REG_DWORD |
20005 |
Specifies the ACG10S data access port number to which to connect. |
|
ACG10S_IMR |
REG_DWORD |
20006 |
|
|
ACG10S_IP |
REG_EXPAND_SZ |
127.0.0.1 |
Specifies the ACG10S remote IP address to which to connect. |
|
ACG10S_Mode |
REG_EXPAND_SZ |
BINARY |
Specifies the communications mode (BINARY or ASCII) |
|
DbgMsgON |
REG_DWORD |
1 |
Enables (1) or disables (0) the internal DM debug messages. |
|
dbgON |
REG_DWORD |
0 |
Debug Flags for ASCII file debugging/diagnostic trace. 0 disables verbose logging while 255 enables the most verbose logging. |
|
LogDays |
REG_DWORD |
0 |
Specifies the number of days of logged data to keep before overwriting the oldest files. |
|
LogMode |
REG_DWORD |
0 |
Specifies the logging mode: (0=create a new log file per day, 1=create a new log file per hour, 2=create a new log file per 10 minutes) |
|
max_poll_cycle |
REG_DWORD |
25000 |
Specifies the maximum time, in milliseconds, between device polls. |
|
MaxDebugLines |
REG_DWORD |
100000 |
Defines the maximum number of debug/log output lines that can be written to the debug files. |
|
MaxIO |
REG_DWORD |
8192 |
Limits the number of tags that the interface will support |
|
PeriodForStats |
REG_DWORD |
1800000 |
Specifies the time interval, in milliseconds, at which the internal DM stat counters are written to the log file. |
|
PollRate |
REG_DWORD |
500 |
Host device poll rate in milliseconds |
|
ReConnectDelay |
REG_DWORD |
3000 |
In the event of a connection being lost, attempts to reconnect in intervals of no shorter than ReConnectDelay milliseconds. |
|
SlotQualityEnabled |
REG_DWORD |
1 |
Enables (1) or disables (0) the monitoring of slot quality |
|
ShowMsg |
REG_DWORD |
1 |
If enabled (1), causes the DM to write operational messages to the log files. |
|
SledgeHammer |
REG_DWORD |
0 |
(1) applies the ACG10S sledgehammer option to the unit. |